T8431 Product datasheet
Model number: |
T8431 |
|
Module Type: |
Analog Input Module |
Manufacture: |
ICS Triplex |
|
Condition: |
Brand New |
Range of Product: |
Trusted TMR System |
|
Lead time: |
In Stock |
Weight: |
1.18kg |
|
HS CODE: |
8537101190 |
Dimension: |
3x30.3x26.4cm |
|
MOQ: |
1 |
Product Origin: |
USA |
|
System: |
PLC |
Discontinued on: |
active |
|
Communication Service: |
Ethernet router |
T8431 Functional Description
Experience unmatched reliability and precision in your industrial automation systems with the T8431 40 High-Performance Analog Input Module from ICS Triplex, a cutting-edge PLC module from the trusted ICS brand. With its T8431 Analog Input Module, you can efficiently handle complex industrial processes, ensuring smooth operation and minimizing downtime.
Equipped with 40 input channels, the T8431 Analog Input Module is designed to process multiple signals simultaneously, making it ideal for demanding industrial applications. Despite its impressive capabilities, it weighs just 1.149 kg, offering a compact yet powerful design that doesn’t compromise on performance.
Built with advanced technology, the T8431 40 Channel Analog Input Module ensures seamless integration with various field devices, offering a comprehensive solution for your automation requirements. Its compatibility with diverse sensors and instruments makes it an invaluable tool for many industrial setups.
Constructed with a durable material coding system, the T8431 40 High-Performance Analog Input Module guarantees long-lasting performance and ensures future-proof operation in the most challenging environments, making it a valuable investment for your business.
If you have other request contact our team to get customized service
ICS Triplex |
T3480 |
ICS Triplex |
T8850C |
ICS Triplex |
T8431 |
ICS Triplex |
T3420A |
ICS Triplex |
T8850 |
ICS Triplex |
T8403 |
ICS Triplex |
T3419 |
ICS Triplex |
T8830C |
ICS Triplex |
T8311 |
ICS Triplex |
T3411F |
ICS Triplex |
T8830 |
ICS Triplex |
T8310C |
ICS Triplex |
T3401 |
ICS Triplex |
T8800 |
ICS Triplex |
T8232 |
ICS Triplex |
T3310 |
ICS Triplex |
T8480 |
ICS Triplex |
T8151B |
ICS Triplex |
T9432 |
ICS Triplex |
T8461CX |
ICS Triplex |
T8122 |
ICS Triplex |
T9451 |
ICS Triplex |
T8461C |
ICS Triplex |
T8110B |
ICS Triplex |
T9310-02 |
ICS Triplex |
T8461 |
ICS Triplex |
T7481A |
ICS Triplex |
T9300 |
ICS Triplex |
T8431C |
ICS Triplex |
T3481A |
Trusted 40 Channel Analogue or Digital Output FTA
The Trusted® 40 Channel Analogue Output or Digital Output Field Termination Assembly (FTA) is designed to act as the main interface between the Trusted Triple Modular Redundant (TMR) 24 Vdc Digital Output Module T8451, Trusted Triple Modular Redundant (TMR) 24/48 Vdc Digital Output Module T84611 or Trusted TMR Analogue Output Module T8480 and the field device.
Recommended proof test methods
Calibration check procedure:24V DC digital outputs
Step A - Set the current to the AI channel 4 mA, verify that the input value is in the range -41 to +41 counts.
Step B - Set the current to the AI channel 12 mA, verify that the input value is in the range 2007 to 2089 counts.
Step C - Set the current to the AI channel 20 mA, verify that the input value is in the range 4055 to 4137 counts.
Step D – Return to Specific Method.
This test is required for all 24V DC DO modules or DC powered NO Contact where Normally De-energized (Energize to Trip) channels (T8850 when used with the T8451, T8461, or T8891 when used with the T8842) are used for Safety-Related Outputs used where the Proof Test frequency >> frequency of Demands. The purpose of this test is to verify that the diodes used for OR’ing the two Field Power sources are not Open circuit, therefore does not constitute a potential undetected dangerous failure. The method described here is the recommended method to verify that neither of the diodes used to OR the 24V DC field supply to a specific T8850 FTA, or the DC supply feeding NO Contact outputs is open circuit. It is assumed that this methodology will be incorporated into a Proof Test procedure that includes other elements of Proof Testing and general proof test requirements as defined in IEC61511.
Method:
Step 1 - If performing this test on a live system, it may be necessary to employ a method external to the Trusted logic solver to mechanically or electrically force any Normally Energized (De Energize to Trip) outputs associated with final elements on the FTA under test into their normal operating state. If not, proceed to Step 2.
Step 2 – Turn off the ‘A’ field supply at an appropriate isolation or termination point and verify that the diode related to ‘B’ supply is correctly providing 24V DC to each power group on the FTA under test.
Step 3 – Return the ‘A’ field supply into service.
Step 4 – Turn off the ‘B’ field supply at an appropriate isolation or termination point and verify that the diode related to ‘A’ supply is correctly providing 24V DC to each power group on the FTA under test.