ICS Triplex T8431 40 Channel Analog Input Module

ICS Triplex T8431
ICS Triplex T8431
ICS Triplex T8431

T8431 Product datasheet 

Model number:

T8431

 

Module Type:

Analog Input Module

Manufacture:

ICS Triplex

 

Condition:

Brand New

Range of Product:

Trusted TMR System

 

Lead time:

In Stock

Weight:

1.18kg

 

HS CODE:

8537101190

Dimension:

3x30.3x26.4cm

 

MOQ:

1

Product Origin:

USA

 

System:

PLC

Discontinued on:

active

 

Communication Service:

Ethernet router

 

T8431 Functional Description 


Experience unmatched reliability and precision in your industrial automation systems with the T8431 40 High-Performance Analog Input Module from ICS Triplex, a cutting-edge PLC module from the trusted ICS brand. With its T8431 Analog Input Module, you can efficiently handle complex industrial processes, ensuring smooth operation and minimizing downtime.

Equipped with 40 input channels, the T8431 Analog Input Module is designed to process multiple signals simultaneously, making it ideal for demanding industrial applications. Despite its impressive capabilities, it weighs just 1.149 kg, offering a compact yet powerful design that doesn’t compromise on performance.

Built with advanced technology, the T8431 40 Channel Analog Input Module ensures seamless integration with various field devices, offering a comprehensive solution for your automation requirements. Its compatibility with diverse sensors and instruments makes it an invaluable tool for many industrial setups.

Constructed with a durable material coding system, the T8431 40 High-Performance Analog Input Module guarantees long-lasting performance and ensures future-proof operation in the most challenging environments, making it a valuable investment for your business.

If you have other request contact our team to get customized service


  •       One Year Warranty

    We offer a one-year warranty for any quality issues with our products. If you encounter any defects or malfunctions during this period, please contact us for prompt resolution. Our warranty covers repairs or replacements, ensuring your satisfaction and peace of mind.

  •         Shipping & Delivery

    We have 10 years experience with leading logistics companies like FedEx, DHL, and SF, ensuring efficient and reliable shipping solutions. Our extensive experience in working with these carriers allows us to offer fast, secure delivery services, tailored to meet the diverse needs of our customers.
  • #

                Payment Method

    We accept a variety of payment methods, including T/T Bank Transfer, Alipay, and more, providing flexible options to suit our customers' preferences. This ensures a convenient and secure transaction process for all orders.
 
How Can I Get Your Support?
Call +86 18159889985 to be connected with our Manager Stella
     Email to sales6@apterpower.com get your best quotation
    For the quick assistance message us on WhatsApp at +86 18159889985 now!
    You can also reach me via Skype: live:ariatang111 or WeChat: zxd18159889985!
 

 

ICS Triplex 

T3480

ICS Triplex

T8850C

ICS Triplex

T8431

ICS Triplex 

T3420A

ICS Triplex

T8850

ICS Triplex

T8403

ICS Triplex

T3419

ICS Triplex

T8830C

ICS Triplex

T8311

ICS Triplex

T3411F

ICS Triplex

T8830

ICS Triplex

T8310C

ICS Triplex

T3401

ICS Triplex

T8800

ICS Triplex

T8232

ICS Triplex

T3310

ICS Triplex

T8480

ICS Triplex

T8151B

ICS Triplex

T9432

ICS Triplex

T8461CX

ICS Triplex

T8122

ICS Triplex

T9451

ICS Triplex

T8461C

ICS Triplex

T8110B

ICS Triplex

T9310-02

ICS Triplex

T8461

ICS Triplex

T7481A

ICS Triplex

T9300

ICS Triplex

T8431C

ICS Triplex

T3481A

 

Trusted 40 Channel Analogue or Digital Output FTA


The Trusted® 40 Channel Analogue Output or Digital Output Field Termination Assembly (FTA) is designed to act as the main interface between the Trusted Triple Modular Redundant (TMR) 24 Vdc Digital Output Module T8451, Trusted Triple Modular Redundant (TMR) 24/48 Vdc Digital Output Module T84611 or Trusted TMR Analogue Output Module T8480 and the field device.

 

Recommended proof test methods


Calibration check procedure:24V DC digital outputs

Step A - Set the current to the AI channel 4 mA, verify that the input value is in the range -41 to +41 counts.

Step B - Set the current to the AI channel 12 mA, verify that the input value is in the range 2007 to 2089 counts.

Step C - Set the current to the AI channel 20 mA, verify that the input value is in the range 4055 to 4137 counts.

Step D – Return to Specific Method.

 

This test is required for all 24V DC DO modules or DC powered NO Contact where Normally De-energized (Energize to Trip) channels (T8850 when used with the T8451, T8461, or T8891 when used with the T8842) are used for Safety-Related Outputs used where the Proof Test frequency >> frequency of Demands. The purpose of this test is to verify that the diodes used for OR’ing the two Field Power sources are not Open circuit, therefore does not constitute a potential undetected dangerous failure. The method described here is the recommended method to verify that neither of the diodes used to OR the 24V DC field supply to a specific T8850 FTA, or the DC supply feeding NO Contact outputs is open circuit. It is assumed that this methodology will be incorporated into a Proof Test procedure that includes other elements of Proof Testing and general proof test requirements as defined in IEC61511.

Method:

Step 1 - If performing this test on a live system, it may be necessary to employ a method external to the Trusted logic solver to mechanically or electrically force any Normally Energized (De Energize to Trip) outputs associated with final elements on the FTA under test into their normal operating state. If not, proceed to Step 2.

Step 2 – Turn off the ‘A’ field supply at an appropriate isolation or termination point and verify that the diode related to ‘B’ supply is correctly providing 24V DC to each power group on the FTA under test.

Step 3 – Return the ‘A’ field supply into service.

Step 4 – Turn off the ‘B’ field supply at an appropriate isolation or termination point and verify that the diode related to ‘A’ supply is correctly providing 24V DC to each power group on the FTA under test.

Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.
Submit

Need Help? Chat with us

Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.
Submit
Looking for News&Events?
Contact Us #
+8618159889985

Our hours

Mon 11/21 - Wed 11/23: 9 AM - 8 PM
Thu 11/24: closed - Happy Thanksgiving!
Fri 11/25: 8 AM - 10 PM
Sat 11/26 - Sun 11/27: 10 AM - 9 PM
(all hours are Eastern Time)

Home

Products

whatsApp

contact